Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 3705 Click

上线3个月,蚂蚁AQ排名冲至中国第7 GTC泽汇资本:白银风头仍劲 铂族金属或成黑马|黄金 陈剖建:银发浪潮下的时代课题——老龄化社会与商业健康险的机遇与挑战 聚力共赢 稳健增长|2025 Swisse 斯维诗合作伙伴大会启幕新征程 “十五五”时期将深化拓展央企“AI+ ”专项行动!央企红利ETF(561580)助力把握央企高质量发展红利 2025年科技行业大赢家:谷歌、马斯克与字节跳动 农业农村部登记推出新一批特色农作物品种1048个 12月22日A股成交额前十大个股,中际旭创(300308)居首 拉萨群众音乐会点燃新年氛围 “高端中国茶第一股”的破与立:八马茶业超级工厂重塑千年茶行业价值逻辑 600800、600250,重大资产重组终止 明年施行!关于人民币现金收付及服务,央行等三部门发文|人民币 终止筹划重组!渤海化学周一复牌 联接东西 智启未来:丁香园与JACC战略合作一周年,共筑中外学术交流新范式 并购潮下头部券商筑生态 区域精兵深耕差异化 聚焦功能跃迁 券商竞合开新局|并购 特朗普向美国高级官员发布《赢得6G竞赛》备忘录 彻底炸了,600221,封单一度超580万手!游戏产业多项数据创新高,三大龙头股涨幅已翻倍!|游戏产业 跑好ESG马拉松,2026《财经》可持续发展论坛成功举行 永赢持股计划刷屏!固总管理规模大幅缩水,这6名基金经理为何落选 航拍黄海东海交汇 大潮奔涌蔚为壮观 烟花概念盘初活跃 华尔泰、凯龙股份双双涨停|华尔泰 评论:赖当局无视民意 终将被反噬 南华期货股份:香港公开发售获1.91倍认购 每股发售价12港元|南华期货股份